Motors & Drives / Motor Starters & Overloads
Contactor Chatter vs. Hum: Telling the Two Faults Apart
- Doc
- contactor-chattering-vs-humming
- Section
- motor-drives/motor-starters
- Revised
A noisy contactor gets treated as one problem, and most troubleshooting lists pile every cause into a single heap — low voltage, dirt, worn contacts, a bad coil. On the panel it is two different faults. One breaks the load and burns contacts in days; the other runs the motor perfectly while making an unpleasant noise. They share almost no causes, and the split takes about thirty seconds to make.
Key Specifications
| Specification | Value | Source |
|---|---|---|
| Conventional AC coil pick-up range, Bulletin 100/104-K | 0.85…1.1 × Us | Rockwell Automation, IEC Contactor Specifications (Technical Data, Bulletin 100/104-K and 100/104-C) — coil pick-up and drop-out limits, coil pick-up vs hold-in burden |
| Conventional AC coil drop-out range, Bulletin 100/104-K | 0.2…0.75 × Us | Rockwell Automation, IEC Contactor Specifications (Technical Data, Bulletin 100/104-K and 100/104-C) — coil pick-up and drop-out limits, coil pick-up vs hold-in burden |
| Conventional AC coil drop-out range, Bulletin 100/104-C | 0.3…0.6 × Us | Rockwell Automation, IEC Contactor Specifications (Technical Data, Bulletin 100/104-K and 100/104-C) — coil pick-up and drop-out limits, coil pick-up vs hold-in burden |
| Electronic DC coil pick-up / drop-out, 100-C frame | pick-up 0.7…1.25 × Us, drop-out 0.3…0.4 × Us | Rockwell Automation, IEC Contactor Specifications (Technical Data, Bulletin 100/104-K and 100/104-C) — coil pick-up and drop-out limits, coil pick-up vs hold-in burden |
| AC coil burden, pick-up vs hold-in, 100-C 09…30 | 75 VA pick-up, 9.5 VA (2.7 W) hold-in | Rockwell Automation, IEC Contactor Specifications (Technical Data, Bulletin 100/104-K and 100/104-C) — coil pick-up and drop-out limits, coil pick-up vs hold-in burden |
| Frequency of shading-ring hum | 100 Hz on a 50 Hz supply, 120 Hz on 60 Hz (two magnetic collapses per cycle) | US Patent 6798323, Welded AC electromagnet lamination assembly incorporating shading coil — armature release at AC zero crossing, shaded pole function |
Types & Variations
Conventional AC coil
Narrow pick-up window and a shading ring in the pole face; pick-up burden several times the hold-in burden.
Use: The default on IEC motor starters. Both fault families apply — it can chatter from a sag and hum from a shading-ring failure.
Electronic wide-band coil
Rectifier and control electronics feed a DC magnet, so the published pick-up window is far wider and there is no shading ring.
Use: Panels with weak or variable control supplies, or a single coil part number across 24…500 V. Rules out shading-ring hum, but masks a degrading supply.
DC-coil contactor
No current zero crossing, so no line-frequency magnetic collapse and no shading ring.
Use: Battery and DC control systems. Line-frequency hum near one of these comes from something else in the enclosure.
Maintenance Steps
- Record the coil terminal voltage during a start, then repeat at the control transformer secondary
Use min/max recording on both readings and compare the minima against Us marked on the coil. Matching sags point at the transformer or its total load; a sag only at the coil puts the loss in the wiring and contacts between them.Live measurement on an energized control circuit requires rated PPE and a meter rated for the installation category. Where the panel cannot be worked live, apply LOTO and test the control circuit from a separate bench supply instead.
- Inspect the pole faces and shading ring with the panel isolated
Apply LOTO, verify absence of voltage on both the power and control sides, then release the contactor and look at the mating faces of yoke and armature. Wipe with a lint-free cloth and a residue-free solvent, and check the copper loop in the pole face for cracks, burned splices, or green corrosion.Do not file, sand, or blast pole faces — removed material becomes a permanent air gap and makes the hum worse than the contamination did.
- Check the seal-in path when coil voltage is healthy but the contactor still chatters
Inspect the NO auxiliary contact carrying the seal-in, the start-button contacts, and every terminal in that loop for looseness or discoloration. An interruption shows on the min/max reading as a collapse to near zero rather than a sag with a floor.Confirm the control circuit is de-energized before pulling wires; a contactor with a held-in armature can hold an energized circuit even after the start button is released.
Split by what the contacts do, not by what you hear
Descriptions of the noise are unreliable — one technician's buzz is another's rattle. The armature state behind the noise is not.
**Chatter**: the armature seals, releases, and seals again. The load actually breaks each cycle. A motor bumps and groans, the overload relay may trip on the repeated inrush, and the main contacts arc on every make. Damage accumulates fast because each cycle is a full switching operation at locked-rotor current.
**Hum**: the armature stays seated and vibrates against the core without breaking. The motor runs normally, current is steady, and the contactor sounds angry but switches nothing. This one is a noise problem first and a reliability problem second.
The measurement that settles it: clamp an ammeter on one motor lead and watch the reading while the noise is happening. Current pulsing toward zero and back is chatter. Steady current under a loud buzz is hum. Without a clamp meter, an unused auxiliary contact wired to a test lamp does the same job — a flickering lamp is chatter.
Everything below assumes you have made this split. Applying the chatter checks to a humming contactor wastes an afternoon on a control circuit that is fine.
Meter the coil terminals during pull-in, not at rest
Chatter driven by voltage drop hides from a static reading. The reason is the burden difference between pulling in and holding: a conventional AC coil in the Bulletin 100-C 09…30 range draws 75 VA at pick-up and 9.5 VA (2.7 W) to hold. The inrush is roughly eight times the sealed burden, so a control transformer or a run of undersized control wire that reads a healthy 118 V at rest can collapse the instant the coil calls for current.
Read across the coil terminals (A1–A2 on IEC-marked units), not at the transformer secondary and not at the start button. Use a meter with min/max recording and press start with the recording armed; a plain averaging reading will not catch a dip that lasts tens of milliseconds. Note the minimum, not the settled value.
Then take the same min/max reading at the transformer secondary during the same operation. The two numbers separate two different faults. A secondary that sags along with the coil is an undersized or overloaded transformer — every other coil, timer, and pilot light on that secondary is sharing the burden. A secondary that holds while the coil dips puts the drop in the wiring and the contacts between them: long runs of 18 AWG (0.75 mm²) control wire, a corroded terminal, a worn start-button contact, or a pitted auxiliary in the seal-in path.
Control wire sized for current alone is a common trap. Control circuits carry very little current, so 18 AWG (0.75 mm²) passes an ampacity check easily and still loses several volts across a long run at 75 VA of inrush.
What the coil voltage number decides
Contactor coils have two published limits, and the gap between them is the chatter band. For Bulletin 100/104-K conventional AC coils, the published pick-up range is 0.85…1.1 × Us and the drop-out range is 0.2…0.75 × Us. The larger 100/104-C frames publish 0.85…1.1 × Us pick-up and 0.3…0.6 × Us drop-out.
Read your recorded minimum against Us on the coil label — the marked coil voltage, not the line voltage.
A minimum that stays above 0.85 × Us clears the control circuit. Stop chasing wiring; the fault is mechanical or in the seal-in path.
A minimum that lands between the drop-out maximum and the pick-up minimum is the chatter band itself, and it is self-sustaining: the coil pulls inrush, the supply sags, the armature releases, the burden drops, the voltage recovers, and it pulls in again. This oscillation is not a symptom of some other fault — the sag and the release feed each other.
Coil voltage that collapses to near zero and returns is a different fault with the same sound. That signature is an intermittent seal-in path, not a sag: a worn NO auxiliary contact, a bouncing safety-relay output, or a loose wire at the start button. Min/max recording tells the two apart because a sag has a floor and an interruption does not.
Electronic wide-band coils publish a much wider window — 0.7…1.25 × Us pick-up with 0.3…0.4 × Us drop-out on the electronic DC coil options for the 100-C frame. Swapping a conventional coil for the electronic version will quiet a marginal circuit, and it is a legitimate fix where the supply is genuinely weak. It is not a fix for a failing transformer or a corroded terminal, both of which keep getting worse behind the wider window.
A hum that survives good coil voltage sits in the magnetic circuit
AC magnetic force collapses at every current zero crossing — 100 times a second on 50 Hz, 120 on 60 Hz. A patent covering AC electromagnet lamination assemblies describes what happens without compensation: "At each zero crossing the spring force may overcome the magnetic force causing the armature to be pushed away and then drawn back again. This can produce a noisy electromagnet." The compensation is a shorted copper turn embedded in the pole face — the shading coil — which carries an induced current phase-shifted from the main flux and holds the armature down through the crossing.
Three things break that, and they are distinguishable without a meter.
**Open or cracked shading ring**: the hum is loud, steady, and tied to line frequency. It will not change no matter how good the coil voltage is, because the coil circuit was never involved. Look for the copper loop set into the pole face; a crack, a burned-open splice, or green corrosion at the joint is a coil-assembly replacement. On most modern contactors the shading ring is not a serviceable part.
**Contaminated or worn pole faces**: rust, hardened oil film, coolant residue, or a wear ridge holds a small air gap that the shading ring cannot close. Sprecher + Schuh lists debris on the pole faces of the yoke and armature among the three causes of contactor noise, alongside coil voltage outside the acceptable range and a control source that cannot supply pick-up current. Clean mating faces with a lint-free cloth and a solvent that leaves no film. Never file or abrasive-blast them — removing material widens the gap permanently, and a filed pole face hums worse than the dirty one did.
**Structure-borne resonance**: the contactor is quiet, the panel is not. Press a gloved finger against the contactor body and then against the mounting rail or door. A hum that changes pitch or drops away under hand pressure on the panel, not the contactor, is a loose DIN rail, an unsupported door, or a wireway lid resonating with a healthy contactor.
A DC-coil contactor has no zero crossing and no shading ring, so line-frequency hum from one is not the contactor. Look at the transformer, a reactor, or another AC-coil device in the same enclosure.
FAQ
My contactor buzzes but the motor runs fine. Do I have to fix it?
The motor running steadily confirms this is hum rather than chatter, so nothing is being switched and there is no arcing damage. The armature is still hammering the core at 100 or 120 times a second, which wears the mating faces and enlarges the gap that caused the noise. Treat it as scheduled work rather than an emergency, and check the pole faces and shading ring at the next shutdown.
Coil voltage measures 120 V at the panel but the contactor still chatters. What now?
A reading at the panel with the contactor at rest tells you almost nothing, because the drop appears only during the pick-up inrush and lasts tens of milliseconds. Repeat the measurement across the coil terminals with min/max recording armed and press start. Compare the recorded minimum, not the resting value, against the coil's marked Us.
Can I just replace the coil?
A new coil helps only when the old one is shorted or open, which shows as a resistance reading well off the published value or as a coil that never pulls in at rated voltage. Chatter caused by supply sag will do exactly the same thing to a new coil. Measure during pull-in before ordering parts.
Does a shading ring get replaced on its own?
Not on most modern contactors — the ring is staked or welded into the laminated pole face, and manufacturers supply it as part of a magnet or coil assembly. Larger frame sizes sometimes list a magnet assembly as a spare, so check the parts breakdown for your frame before deciding to replace the whole device.
References
- Rockwell Automation, IEC Contactor Specifications (Technical Data, Bulletin 100/104-K and 100/104-C) — coil pick-up and drop-out limits, coil pick-up vs hold-in burden
- Sprecher + Schuh, Causes of Unexpected Contactor Noise — coil voltage out of range, insufficient pick-up current, debris on pole faces
- US Patent 6798323, Welded AC electromagnet lamination assembly incorporating shading coil — armature release at AC zero crossing, shaded pole function
- IEC, Low-voltage switchgear and controlgear — electromechanical contactors and motor-starters
Spotted an error or have a question about this guide? Email contact@fixtheplant.com — corrections are prioritized.